Nationwide Boiler's 90,000 pph, 650 psig saturated steam, trailer-mounted package watertube boiler is set to burn natural gas (#2 oil is optional). It is fully piped and wired and includes a low NOx burner, EconoStak economizer, PLC-based control system, non-return valve and steam stub stack. Optional CataStakā„¢ SCR System can be supplied for as low as 2.5 ppm NOx performance.
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Design Pressure

N/A 650 psig

Operating Pressure

N/A 150 to 600 psig

Boiler Capacity

N/A 90,000 lb/hr

Fuel Consumption

Natural Gas Consumption Rate1 N/A 110,680 SCFH

Connection Sizes

Main Steam Connection Size

N/A 8 in

Main Steam Connection Type

N/A 600# FLG

Natural Gas Connection Size

N/A 4 in

Natural Gas Connection Type

N/A 150# FLG

Feedwater Connection Size

N/A 3 in

Feedwater Connection Type

N/A 600# FLG

Bottom Blowdown Connection Size

N/A 1-1/2 in

Bottom Blowdown Connection Type

N/A 600# FLG

Continuous Blowdown Connection Size

N/A 1 in

Continuous Blowdown Connection Type

N/A NPT

Instrument Air Connection Size

N/A 1/2 in

Instrument Air Connection Type

N/A NPT

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 480 VAC, 3 ph, 60 hz, 250 AMPS

Dimensions and Weights

Length

N/A 51 ft 9 in.

Width

N/A 11 ft 0 in.

Height

N/A 14 ft 0 in.

Shipping Weight

N/A 136,000 lb

Operating Weight

N/A 167,287 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 30 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm

Additional Information

Additional Information

N/A Nationwide Boiler's low NOx 90,000 pph, 650 psig design (150 - 600 psig operating), saturated steam, trailer-mounted Superior package watertube boiler is set to burn natural gas or future #2 oil. It is fully piped and wired and includes the following components:
  • Low NOx Burner
  • Burner Management System
  • Rectangular Economizer with Piping (loose)
  • Parallel Positioning Combustion Controls
  • Forced Draft Fan & Motor (loose)
  • Complete Fuel Train & Pilot Ignition System
  • Water Column & Site Glass
  • Steam Pressure Gauge
  • Low-water Cutoffs
  • Safety Valves
  • Feedwater Stop & Check Valves
  • Blowdown Valves
  • Continuous Blowdown Metering Valve
  • Chemical Feed Valve
  • Single Element Feedwater Regulator with Pre-piped 3-Valve Bypass
  • Steam Non-return Valve
  • FGR Ductwork (loose)
  • Stack (loose)
  • NEMA 4 Electrical Enclosures
  • Low NOx CataStakā„¢ SCR System (optional)
  • Weatherproofed (except for freezing)
  • Meets FM, NFPA 85 & IRI Insurance Standards
  • Electronic Operating Manuals

Note

Note

N/A Actual Equipment may differ from listed specification.
  • 1 At 12 psi regulated pressure