Brands |
N/A Nationwide Boiler's |
Design Pressure |
N/A 750 psig |
Operating Pressure |
N/A 250 to 675 psig |
Boiler Capacity |
N/A 85,000 lb/hr |
Natural Gas Consumption Rate1 | N/A 123,000 SCFH |
Number 2 Fuel Oil Consumption Rate2 | N/A 861 gal/h |
Main Steam Connection Size |
N/A 8 in |
Main Steam Connection Type |
N/A 600# FLG |
Natural Gas Connection Size |
N/A 4 in |
Natural Gas Connection Type |
N/A 150# FLG |
Number 2 Fuel Oil Supply Connection Size |
N/A 1 in |
Number 2 Fuel Oil Supply Connection Type |
N/A 150# R.F FLG |
Feedwater Connection Size |
N/A 2-1/2 in |
Feedwater Connection Type |
N/A 600# FLG |
Bottom Blowdown Connection Size |
N/A 1-1/2 in |
Bottom Blowdown Connection Type |
N/A 600# FLG |
Continuous Blowdown Connection Size |
N/A 1 in |
Continuous Blowdown Connection Type |
N/A NPT |
Chemical Feed Connection Size |
N/A 1 |
Chemical Feed Connection Type |
N/A NPT |
Atomizing Steam Connection Size |
N/A 1 in |
Atomizing Steam Connection Type |
N/A NPT |
Instrument Air Connection Size |
N/A 1/2 in |
Instrument Air Connection Type |
N/A NPT |
Water Column Drain Connection Size |
N/A 2 in |
Water Column Drain Connection Type |
N/A 600# R.F FLG |
Electrical Power Service Requirements |
N/A 480 VAC, 3 ph, 60 hz, 250 AMPS |
Length3 | N/A 95 ft 4 in. |
Width |
N/A 11 in. |
Height |
N/A 14 ft 0 in. |
Shipping Weight |
N/A 180,827 lb |
Operating Weight (With Economizer)4 | N/A 170,032 lb |
Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) |
N/A 30 ppm |
Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) |
N/A 50 ppm |
Additional Information |
N/A
Nationwide Boiler's low NOx, 85,000 pph, 750 psig (250-675 psig operating) / 750ºF design superheat, trailer-mounted Superior package watertube boiler is set to burn natural gas (#2 oil is optional). It is fully piped and wired and includes the following components:
|