COMPANY HEADER
Print Back
Nationwide Boiler's 85,000 pph, 750 psig / 750ºF superheat, trailer-mounted package watertube boiler is set to burn natural gas (#2 oil is optional). It is fully piped and wired and includes a low NOx burner, EconoStak economizer, PLC-based control system, non-return valve and steam stub stack. Optional CataStak™ SCR System can be supplied for ultra low NOx compliance.
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Design Pressure

N/A 750 psig

Operating Pressure

N/A 250 to 675 psig

Boiler Capacity

N/A 85,000 lb/hr

Fuel Consumption

Natural Gas Consumption Rate1 N/A 123,000 SCFH
Number 2 Fuel Oil Consumption Rate2 N/A 861 gal/h

Connection Sizes

Main Steam Connection Size

N/A 8 in

Main Steam Connection Type

N/A 600# FLG

Natural Gas Connection Size

N/A 4 in

Natural Gas Connection Type

N/A 150# FLG

Number 2 Fuel Oil Supply Connection Size

N/A 1 in

Number 2 Fuel Oil Supply Connection Type

N/A 150# R.F FLG

Feedwater Connection Size

N/A 2-1/2 in

Feedwater Connection Type

N/A 600# FLG

Bottom Blowdown Connection Size

N/A 1-1/2 in

Bottom Blowdown Connection Type

N/A 600# FLG

Continuous Blowdown Connection Size

N/A 1 in

Continuous Blowdown Connection Type

N/A NPT

Chemical Feed Connection Size

N/A 1

Chemical Feed Connection Type

N/A NPT

Atomizing Steam Connection Size

N/A 1 in

Atomizing Steam Connection Type

N/A NPT

Instrument Air Connection Size

N/A 1/2 in

Instrument Air Connection Type

N/A NPT

Water Column Drain Connection Size

N/A 2 in

Water Column Drain Connection Type

N/A 600# R.F FLG

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 480 VAC, 3 ph, 60 hz, 250 AMPS

Dimensions and Weights

Length3 N/A 95 ft 4 in.

Width

N/A 11 in.

Height

N/A 14 ft 0 in.

Shipping Weight

N/A 180,827 lb
Operating Weight (With Economizer)4 N/A 170,032 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 30 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm

Additional Information

Additional Information

N/A Nationwide Boiler's low NOx, 85,000 pph, 750 psig (250-675 psig operating) / 750ºF design superheat, trailer-mounted Superior package watertube boiler is set to burn natural gas (#2 oil is optional). It is fully piped and wired and includes the following components:
  • Low NOx Burner
  • EconoStak Economizer
  • Burner Management System
  • Parallel Positioning Combustion Controls
  • Forced Draft Fan, Motor & Starter
  • Complete Fuel Train & Pilot Ignition System
  • Water Column & Site Glass
  • Steam Pressure Gauge
  • Low-water Cutoffs
  • Safety Valves
  • Feedwater Stop & Check Valves
  • Blowdown Valves
  • Continuous Blowdown Metering Valve
  • Chemical Feed Valve
  • Single Element Feedwater Regulator with Pre-piped 3-Valve Bypass
  • Steam Non-return Valve (loose)
  • Stack (loose)
  • NEMA 4 Electrical Enclosures
  • Separate Fuel Oil Skid for #2 Oil Firing (optional)
  • Low NOx CataStak SCR System (optional)
  • Weatherproofed (except for freezing)
  • Meets FM, NFPA 85 & IRI Insurance Standards
  • Operating Manuals
  • 1 At 15 psi regulated pressure
  • 2 At 150 psi regulated pressure
  • 3 Actual Equipment may differ from listed specification.