COMPANY HEADER
Print Back
Nationwide Boiler's ultra-low NOx, 80 hp (2,760 lbs/hr) Mobile Boiler Room is an enclosed van unit, designed at 200 psig pressure, firing natural gas (LPG is optional). It is fully piped and wired and includes a firetube boiler, ultra low NOx burner, gas pressure regulator, feedwater system, water softener, chemical feed system, blowdown separator, control panel and valve trim (headers, safeties, blowdown, etc.).
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Natural Gas Consumption Rate

N/A 3,360 SCFH

Design Pressure

N/A 200 psig

Boiler Capacity

N/A 80 hp

NBI Tag #

N/A B674

Connection Sizes

Main Steam Connection Size

N/A 3 in

Main Steam Connection Type

N/A 250# FLG

Natural Gas Connection Size

N/A 2 in

Natural Gas Connection Type

N/A FLG

Blowdown/Drain Connection Size

N/A 2-1/2 in

Blowdown/Drain Connection Type

N/A 150# FLG

Condensate Return Connection Size

N/A 1-1/2 in

Condensate Return Connection Type

N/A NPT

Make-Up Water Connection Size

N/A 1 in

Make-Up Water Connection Type

N/A NPT

Softener Drain Connection Size

N/A 1 in

Softener Drain Connection Type

N/A NPT

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 480 VAC, 3 ph, 60 hz, 50 AMPS

Dimensions and Weights

Length

N/A 27.0 ft

Width

N/A 8.0 ft

Height

N/A 13.0 ft

Shipping Weight

N/A 21,400 lb

Operating Weight

N/A 27,500 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 9 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm