Brands |
N/A Nationwide Boiler's |
Design Pressure |
N/A 750 psig |
Operating Pressure |
N/A 250 to 675 psig |
Operating Temperature |
N/A 750 ºF |
Boiler Capacity |
N/A 75,000 lb/hr |
NBI Tag # |
N/A Various |
Natural Gas Consumption Rate1 | N/A 107,500 SCFH |
Number 2 Fuel Oil Consumption Rate |
N/A 765 gal/h |
Main Steam Connection Size |
N/A 8 in |
Main Steam Connection Type |
N/A 600# FLG |
Natural Gas Connection Size |
N/A 6 in |
Natural Gas Connection Type |
N/A 125# FLG |
Number 2 Fuel Oil Supply Connection Size |
N/A 2 in |
Number 2 Fuel Oil Supply Connection Type |
N/A NPT |
Number 2 Fuel Oil Return Connection Size |
N/A 1-1/4 in |
Number 2 Fuel Oil Return Connection Type |
N/A NPT |
Feedwater Connection Size |
N/A 2-1/2 in |
Feedwater Connection Type |
N/A 600# FLG |
Bottom Blowdown Connection Size |
N/A 1-1/2 in |
Bottom Blowdown Connection Type |
N/A 600# FLG |
Continuous Blowdown Connection Size |
N/A 3/4 in |
Continuous Blowdown Connection Type |
N/A NPT |
Chemical Feed Connection Size |
N/A 1/2 in |
Chemical Feed Connection Type |
N/A NPT |
Atomizing Air Connection Size |
N/A 2 in |
Atomizing Air Connection Type |
N/A NPT |
Atomizing Steam Connection Size |
N/A 3 in |
Atomizing Steam Connection Type |
N/A 150# FLG |
Instrument Air Connection Size |
N/A 1/2 in |
Instrument Air Connection Type |
N/A NPT |
Water Column Drain Connection Size |
N/A 3/4 in |
Water Column Drain Connection Type |
N/A NPT |
Electrical Power Service Requirements |
N/A 480 VAC, 3 ph, 60 hz, 200 AMPS |