COMPANY HEADER
Print Back
Nationwide Boiler's ultra-low NOx, 650 hp (22,500 lbs/hr) Mobile Boiler Room is an enclosed van unit, designed at 250 psig pressure, firing natural gas (LPG is optional). It is fully piped and wired and includes a firetube boiler, ultra low NOx burner, gas pressure regulator, feedwater system, water softener, chemical feed system, blowdown separator, control panel and valve trim (headers, safeties, blowdown, etc.).
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Boiler Capacity

N/A 650 hp

Design Pressure

N/A 200 psig

NBI Tag #

N/A B552 B729 B759 B780

Fuel Consumption

Natural Gas Consumption Rate1 N/A 28,800 SCFH

Connection Sizes

Main Steam Connection Size

N/A 6 in

Main Steam Connection Type

N/A 250# FLG (Valve Outlet)

Natural Gas Connection Size

N/A 3 in

Natural Gas Connection Type

N/A 150# FLG

Blowdown/Drain Connection Size

N/A 6 in

Blowdown/Drain Connection Type

N/A 150# FLG

Condensate Return Connection Size

N/A 1-1/2 in

Condensate Return Connection Type

N/A NPT ea. for Low and High Temperature

Make-Up Water Connection Size

N/A 1-1/2 in

Make-Up Water Connection Type

N/A NPT (60 to 100 psig)

Softener Drain Connection Size

N/A 2 in

Softener Drain Connection Type

N/A NPT

Instrument Air Connection Size

N/A 1/2 in

Instrument Air Connection Type

N/A NPT

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 460 VAC, 3 ph, 60 hz, 150 AMPS

Dimensions and Weights

Length

N/A 48 ft 0 in.

Width

N/A 8 ft 6 in.

Height

N/A 13 ft 11 in.

Shipping Weight

N/A 72,500 lb

Operating Weight

N/A 116,900 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 9 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm
  • 1 At 10 to 25 psig pressure