COMPANY HEADER
Print Back
Nationwide Boiler's low NOx, 50 hp (1,725 lbs/hr) Mobile Boiler Room is an enclosed van unit, designed at 250 psig pressure, firing natural gas or #2 oil. It is fully piped and wired and includes a firetube boiler, low NOx burner, gas pressure regulator, feedwater system, water softener, chemical feed system, blowdown separator, control panel and valve trim (headers, safeties, blowdown, etc.).
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Boiler Capacity

N/A 50 hp1,725 lb/hr

Design Pressure

N/A 250 psig

NBI Tag #

N/A B578

Fuel Consumption

Number 2 Fuel Oil Consumption Rate

N/A 15 gal/h

LPG Consumption Rate

N/A 23 gal/h
Natural Gas Consumption Rate1 N/A 2,095 SCFH

Connection Sizes

Main Steam Connection Size

N/A 3 in

Main Steam Connection Type

N/A 300# RF FLG

Natural Gas/LPG Connection Size

N/A 2 in

Natural Gas/LPG Connection Type

N/A 150# FF FLG

Number 2 Fuel Oil Supply Connection Size

N/A 3/4 in

Number 2 Fuel Oil Supply Connection Type

N/A NPT

Number 2 Fuel Oil Return Connection Size

N/A 1/2 in

Number 2 Fuel Oil Return Connection Type

N/A NPT

Blowdown/Drain Connection Size

N/A 4 in

Blowdown/Drain Connection Type

N/A 150# RF FLG

Condensate Return Connection Size

N/A 2 in

Condensate Return Connection Type

N/A NPT

Make-Up Water Connection Size

N/A 1 in

Make-Up Water Connection Type

N/A NPT (60 to 100 psig)

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 460 VAC, 3 ph, 60 hz, 60 AMPS

Dimensions and Weights

Length

N/A 20.0 ft

Width

N/A 8.0 ft

Height

N/A 8.6 ft

Shipping Weight

N/A 17,700 lb

Operating Weight

N/A 22,600 lb
  • 1 At 10 psig pressure