COMPANY HEADER
Print Back
Nationwide Boiler's low NOx, 300 hp (10,350 lbs/hr) Mobile Boiler Room is an enclosed van unit, designed at 250 psig pressure, firing natural gas or #2 oil. It is fully piped and wired and includes a firetube boiler, low NOx burner, gas pressure regulator, feedwater system, water softener, chemical feed system, blowdown separator, control panel and valve trim (headers, safeties, blowdown, etc.).
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Boiler Capacity

N/A 300 hp10,350 lb/hr

Design Pressure

N/A 250 psig

NBI Tag #

N/A B554

Features

N/A Low Nitrogen Oxide (NOx) Emission

Fuel Consumption

Natural Gas Consumption Rate at 10 Pounds per Square Inch Gauge (psig)

N/A 12,600 SCFH

Number 2 Fuel Oil Consumption Rate at 250 Pounds per Square Inch Gauge (psig)

N/A 90 gal/h

Connection Sizes

Main Steam Connection Size

N/A 6 in

Main Steam Connection Type

N/A 300# FLG

Natural Gas Connection Size

N/A 2-1/2 in

Natural Gas Connection Type

N/A 150# FLG

Blowdown/Drain Connection Size

N/A 6 in

Blowdown/Drain Connection Type

N/A 150# FLG

Condensate Return Connection Size

N/A 1-1/2 in

Condensate Return Connection Type

N/A NPT

Make-Up Water Connection Size

N/A 1-1/2 in

Make-Up Water Connection Type

N/A NPT

Softener Drain Connection Size

N/A 1-1/2 in

Softener Drain Connection Type

N/A NPT

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 460 VAC, 3 ph, 60 hz, 175 AMPS

Dimensions and Weights

Length

N/A 48 ft 0 in.

Width

N/A 8 ft 6 in.

Height

N/A 13 ft 8-1/2 in.

Approximate Shipping Weight

N/A 45,000 lb

Approximate Operating Weight

N/A 60,000 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 30 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm

Note

Note

N/A Actual Equipment may differ from listed specification.