Brands |
N/A Nationwide Boiler's |
Storage Capacity |
N/A 3,300 gal |
Steam Requirements at 60 Pounds per Square Inch Gauge (psig) Regulation Pressure |
N/A 32,725 lb/hr |
Condensate Returns |
N/A 0 % |
Total Feedwater Pumps |
N/A 4 |
Carver Pump |
N/A Multi Stage |
Each Feedwater Pumps Capacity |
N/A 195 gpm |
Total Discharge Head |
N/A 1,750 ft |
Boiler Capacity |
N/A 225,000 lb/hr |
Design Pressure |
N/A 50 psig |
NBI Tag # |
N/A 193 212 FS1192 |
Deaerator Steam Supply Connection Size |
N/A 4 in |
Deaerator Steam Supply Connection Type |
N/A 300# FLG |
Make-Up Water Connection Size |
N/A 4 in |
Make-Up Water Connection Type |
N/A 150# FLG |
Condensate Connection Size |
N/A 6 in |
Condensate Connection Type |
N/A 150# FLG |
Overflow Connection Size |
N/A 6 in |
Overflow Connection Type |
N/A 150# FLG |
Drain Connection Size |
N/A 3 in |
Drain Connection Type |
N/A 150# FLG |
Cooling Water Inlet Connection Size |
N/A 1/2 in |
Cooling Water Inlet Connection Type |
N/A NPT |
Cooling Water Outlet Connection Size |
N/A 1/2 in |
Cooling Water Outlet Connection Type |
N/A NPT |
Instrument Air Connection Size |
N/A 1/2 in |
Instrument Air Connection Type |
N/A NPT |
Feedwater Discharge Connection Size |
N/A 6 in |
Feedwater Discharge Connection Type |
N/A 600# FLG |
Electrical Power Service Requirements |
N/A 480 VAC, 3 ph, 60 hz, 1000 AMPS (each motor 250 AMPS) |
Shipping Height |
N/A 8 ft 3 in. |
Shipping Length |
N/A 32 ft 7 in. |
Shipping Width |
N/A 9 ft 1 in. |
Shipping Weight |
N/A 48,500 lb |
Shipping Loads |
N/A 2 |
Assembled Height |
N/A 26 ft 7 in. |
Assembled Length |
N/A 32 ft 7 in. |
Assembled Width |
N/A 9 ft 1 in. |
Operating Weight |
N/A 76,850 lb |
Flooded Weight |
N/A 93,500 lb |