COMPANY HEADER
Print Back
Nationwide Boiler's 150,000 pph, 650 psig saturated steam, skid-mounted package watertube boiler is set to burn natural gas (#2 oil is optional). It is fully piped and wired and includes a low NOx burner, EconoStak economizer, PLC-based control system, non-return valve and steam stub stack. Optional CataStakā„¢ SCR System can be supplied for as low as 2.5 ppm NOx performance.
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Design Pressure

N/A 650 psig

Operating Pressure

N/A 150 to 600 psig

Boiler Capacity

N/A 150,000 lb/hr

Fuel Consumption

Natural Gas Consumption Rate1 N/A 181,000 SCFH

Connection Sizes

Main Steam Connection Size

N/A 8 in

Main Steam Connection Type

N/A 600# FLG

Natural Gas Connection Size

N/A 4 in

Natural Gas Connection Type

N/A 150# FLG

Feedwater Connection Size

N/A 4 in

Feedwater Connection Type

N/A 600# FLG

Bottom Blowdown Connection Size

N/A 1-1/2 in

Bottom Blowdown Connection Type

N/A 600# FLG

Continuous Blowdown Connection Size

N/A 1 in

Continuous Blowdown Connection Type

N/A 800# FLG

Chemical Feed Connection Size

N/A 1

Chemical Feed Connection Type

N/A 800# FLG

Instrument Air Connection Size

N/A 1 in

Instrument Air Connection Type

N/A NPT

Water Column Drain Connection Size

N/A 2 in

Water Column Drain Connection Type

N/A NPT

Electrical Power Service Requirements

Electrical Power Service Requirements2 N/A 480 VAC, 3 ph, 60 hz, 300 HP Standard

Dimensions and Weights

Length (Boiler Only)

N/A 34 ft 0 in.

Width (Installed)

N/A 11 ft 2 in.

Height (Installed with Economizer)

N/A 40 ft 0 in.

Shipping Weight (With Trailer)

N/A 220,000 lb

Operating Weight (With Economizer)

N/A 207,000 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) Without Selective Catalytic Reduction (SCR)3 N/A 30 ppm83 ppm
Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) Without Selective Catalytic Reduction (SCR)4 N/A 50 ppm

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) With Selective Catalytic Reduction (SCR)

N/A 5 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) With Selective Catalytic Reduction (SCR)

N/A 50 ppm

Additional Information

Additional Information

N/A
  • Low NOx Burner
  • Burner Management System
  • EconoStak Economizer
  • PLC-Based, Fully Metered Combustion Controls
  • Forced Draft Fan, Motor & Starter
  • Complete Fuel Train & Pilot Ignition System
  • Water Column & Site Glass
  • Steam Pressure Gauge
  • Low-water Cutoffs
  • Safety Valves
  • Pre-piped Feedwater Stop & Check Valves
  • Pre-piped Blowdown Valves
  • Continuous Blowdown Metering Valve
  • Chemical Feed Valve
  • Steam Non-return Valve (loose)
  • Stack (loose)
  • Economizer with Structure (loose)
  • NEMA 4 Electrical Enclosures
  • Weatherproofed (except for freezing)
  • Meets FM, NFPA 85 & IRI Insurance Standards
  • Operating Manuals and Drawings on CD
  • CataStakā„¢ SCR System for 5 ppm NOx (optional)
  • 1 At 25 psi pressure
  • 2 Actual Equipment may differ from listed specification.
  • 3 Capacity derated to 135,000 pph
  • 4 Capacity derated to 135,000 pph