COMPANY HEADER
Print Back
Nationwide Boiler's low NOx, 1000 hp (34,500 lbs/hr) Mobile Boiler Room is an enclosed van unit, designed at 290 psig pressure, firing natural gas or #2 oil. It is fully piped and wired and includes a firetube boiler, low NOx burner, gas pressure regulator, feedwater system, chemical feed system, blowdown separator, control panel and valve trim (headers, safeties, blowdown, etc.).
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Boiler Capacity

N/A 1,000 hp34,500 lb/hr

Design Pressure

N/A 290 psig

Operating Pressure

N/A 100 to 260 psig

Shipping Weight

N/A 97,960 lb

NBI Tag #

N/A B740 B800

Features

N/A Low Nitrogen Oxide (NOx) Emission

Fuel Consumption

Natural Gas Consumption Rate at 2 Pounds per Square Inch Gauge (psig) Regulated

N/A 39,900 SCFH

Number 2 Fuel Oil Consumption Rate

N/A 300 gal/h

Connection Sizes

Main Steam Connection Size

N/A 6 in

Main Steam Connection Type

N/A 300# FLG

Natural Gas Connection Size

N/A 3 in

Natural Gas Connection Type

N/A 150# FLG

Number 2 Fuel Oil Supply Connection Size

N/A 1 in

Number 2 Fuel Oil Supply Connection Type

N/A NPT

Number 2 Fuel Oil Return Connection Size

N/A 3/4 in

Number 2 Fuel Oil Return Connection Type

N/A NPT

Atomizing Air Connection Size

N/A 3/4 in

Atomizing Air Connection Type

N/A NPT

Auxiliary Feedwater Connection Size

N/A 2 in

Auxiliary Feedwater Connection Type

N/A NPT

Blowdown/Drain Connection Size

N/A 6 in

Blowdown/Drain Connection Type

N/A 150# FLG

Condensate Return Connection Size

N/A 2 in

Condensate Return Connection Type

N/A NPT for Low and High Temperature

Make-Up Water Connection Size

N/A 2 in

Make-Up Water Connection Type

N/A NPT

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 460 VAC, 3 ph, 60 hz, 175 AMPS

Dimensions and Weights

Length

N/A 53 ft 10 in.

Width

N/A 8 ft 6 in.

Height

N/A 13 ft 10 in.

Operating Weight

N/A 132,140 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 30 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm

Note

Note

N/A Actual Equipment may differ from listed specification.