COMPANY HEADER
Request Information
Nationwide Boiler's ultra-low NOx, 350 hp (12,075 lbs/hr) Mobile Boiler Room is an enclosed van unit, designed at 250 psig pressure, firing natural gas (LPG is optional). It is fully piped and wired and includes a firetube boiler, ultra low NOx burner, gas pressure regulator, feedwater system, water softener, chemical feed system, blowdown separator, control panel and valve trim (headers, safeties, blowdown, etc.).
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Boiler Capacity

N/A 12,075 lb/hr350 hp

Design Pressure

N/A 250 psig

Fuel Consumption

Natural Gas Consumption Rate1 N/A 16,130 SCFH
Propane Consumption Rate2 N/A 150 gal/h

Connection Sizes

Main Steam Connection Size

N/A 6 in

Main Steam Connection Type

N/A 250# FLG

Natural Gas Connection Size

N/A 2-1/2 in

Natural Gas Connection Type

N/A 150# FLG

Blowdown/Drain Connection Size

N/A 8 in

Blowdown/Drain Connection Type

N/A 150# FLG

Condensate Return Connection Size

N/A 1-1/2 in

Condensate Return Connection Type

N/A NPT
Make-Up Water Connection Size3 N/A 1-1/2 in
Make-Up Water Connection Type4 N/A NPT

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 460 VAC, 3 ph, 60 hz, 100 AMPS

Dimensions and Weights

Length

N/A 48 ft 0 in.

Width

N/A 8 ft 6 in.

Height

N/A 13 ft 5 in.

Shipping Weight

N/A 54,300 lb

Operating Weight

N/A 70,000 lb

Emissions Data (Natural Gas)

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 9 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm

Additional Information

Additional Information

N/A Nationwide Boiler's ultra low NOx, 350 hp (12,075 lbs/hr) Superior Mobile Room is an enclosed van unit, designed at 250 psig pressure, firing natural gas/propane. It is fully piped and wired and includes the following components:
  • 350 hp Package Firetube Boiler
  • Ultra Low Nox Burner
  • Gas Pressure Regulator
  • Control Panel w/ Remote Communications Package
  • Valve Trim (header, safeties, blowdown, etc.)
  • Duplex Feedwater System w/ Condensate Return Tank & Preheater
  • Duplex Water Softener
  • Chemical Feed System
  • Blowdown Separator
  • Sample Cooler & Sink
  • Interior Lighting
  • Stack (loose)
  • Operating Manuals

Note

Note

N/A Actual Equipment may differ from listed specification.
  • 1 At 25 psig maximum pressure
  • 2 At 25 psig maximum pressure
  • 3 At 60 to 100 psig regulated pressure
  • 4 At 60 to 100 psig regulated pressure