COMPANY HEADER
Request Information
Nationwide Boiler's ultra-low NOx, 200 hp (6,900 lbs/hr) Mobile Boiler Room is an enclosed van unit, designed at 250 psig pressure, firing natural gas (LPG is optional). It is fully piped and wired and includes a firetube boiler, ultra low NOx burner, gas pressure regulator, feedwater system, water softener, chemical feed system, blowdown separator, control panel and valve trim (headers, safeties, blowdown, etc.).
Unit of Measure

Specifications

Brands

N/A Nationwide Boiler's

Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 9 ppm

Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2))

N/A 50 ppm

Boiler Capacity

N/A 6,900 lb/hr200 hp

Design Pressure

N/A 250 psig

NBI Tag #

N/A B662

Fuel Consumption

Natural Gas Consumption Rate1 N/A 8,400 SCFH

LPG Consumption Rate

N/A 92 gal/h

Connection Sizes

Main Steam Connection Size

N/A 6 in

Main Steam Connection Type

N/A 300# FLG

Natural Gas/LPG Connection Size

N/A 3 in

Natural Gas/LPG Connection Type

N/A 150# FLG

Blowdown/Drain Connection Size

N/A 4 in

Blowdown/Drain Connection Type

N/A 150# FLG

Condensate Return Connection Size

N/A 1-1/2 in

Condensate Return Connection Type

N/A NPT

Make-Up Water Connection Size

N/A 1-1/2 in

Make-Up Water Connection Type

N/A NPT (60 to 100 psig)

Softener Drain Connection Size

N/A 2 in

Softener Drain Connection Type

N/A 150# FLG

Electrical Power Service Requirements

Electrical Power Service Requirements

N/A 480 VAC, 3 ph, 60 hz, 75 AMPS

Dimensions and Weights

Length

N/A 53 ft 0 in.

Width

N/A 8 ft 6 in.

Height

N/A 13 ft 6 in.

Shipping Weight

N/A 55,840 lb

Operating Weight

N/A 70,000 lb
  • 1 At 9 psig pressure