Brands |
N/A Nationwide Boiler's |
Natural Gas Consumption Rate1 | N/A 156,000 SCFH |
Design Pressure |
N/A 750 psig |
Operating Pressure |
N/A 350 to 650 psig |
Operating Temperature |
N/A 750 ºF |
Boiler Capacity |
N/A 110,000 lb/hr |
NBI Tag # |
N/A B777 |
Main Steam Connection Size |
N/A 8 in |
Main Steam Connection Type |
N/A 600# FLG |
Natural Gas Connection Size |
N/A 4 in |
Natural Gas Connection Type |
N/A 150# FLG |
Feedwater Connection Size |
N/A 3 in |
Feedwater Connection Type |
N/A 600# FLG |
Bottom Blowdown Connection Size |
N/A 1-1/2 in |
Bottom Blowdown Connection Type |
N/A 600# FLG |
Continuous Blowdown Connection Size |
N/A 1 in |
Continuous Blowdown Connection Type |
N/A 600# FLG |
Chemical Feed Connection Size |
N/A 1/2 in |
Chemical Feed Connection Type |
N/A 600# FLG |
Instrument Air Connection Size |
N/A 3/4 in |
Instrument Air Connection Type |
N/A NPT |
Water Column Drain Connection Size |
N/A 3/4 in |
Water Column Drain Connection Type |
N/A NPT |
Electrical Power Service Requirements |
N/A 480 VAC, 3 ph, 60 hz, 400 AMPS |
Length |
N/A 30 ft 5 in. (Boiler Only) |
Width |
N/A 11 ft 11-1/2 in. (Installed) |
Height |
N/A 40 ft 0 in. (Installed with Economizer) |
Shipping Weight2 | N/A 219,800 lb |
Operating Weight3 | N/A 170,000 lb |
Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) Without Selective Catalytic Reduction (SCR)4 | N/A 80 ppm |
Nitrogen Oxide (NOx) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) With Selective Catalytic Reduction (SCR) |
N/A 5 ppm30 ppm |
Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) Without Selective Catalytic Reduction (SCR) |
N/A 50 ppm |
Carbon Monoxide (CO) Emission Rate (Correlated to 3 Percent (%) Oxygen (O2)) With Selective Catalytic Reduction (SCR) |
N/A 50 ppm |